24F SM Armored MTP Trunk Cable -3.5mm
The 24-fiber single-mode armored MTP-MTP trunk cable is an ultra-high-density optical interconnect engineered for next-generation data center and telecom backbones. Terminated with dual-row 24F MTP connectors on both ends, it delivers maximum fiber density while the armored 3.0mm cable ensures superior mechanical protection for customizable long-reach deployments.
Description
Design Principles
Armored 3.0mm Construction. The cable integrates a stainless steel interlock armor layer providing ≥440 N/10 cm crush resistance, rodent protection, and impact resistance. The 3.0mm outer diameter balances rugged durability with optimal cable tray fill efficiency, eliminating the need for external conduits in exposed runs.
Dual-Row MTP Technology. Utilizes a precision-molded dual-row MT ferrule housing 24 single-mode fibers in a 2×12 array. Stainless steel guide pins ensure sub-micron alignment, available in Type A/B/C polarity per TIA-568.2 to support complex parallel optical architectures.
Single-Mode Performance. Equipped with ITU-T G.652D/G.657A2 fibers (≤0.20 dB/km at 1550 nm) for extended reach up to 80+ km. MTP connectors achieve ≤0.25 dB insertion loss and ≥60 dB return loss (APC ≥65 dB). 100% tested via IEC 61300-3-35 interferometry.
Environmental Compliance. LSZH/OFNP jackets meet IEC and NFPA flame/smoke standards. Operating temperature: -20°C to +70°C.
| Spec items. | Single mode (APC 8-degree polished) | Multimode (PC Flat polish) |
| Insertion loss (MPO)
(IEC 61300-3-34) |
Standard MTP:≤0.75dB(max),≤0.35dB(Typical)
Elite MTP:≤0.35dB(max),≤0.20dB(Typical) |
Standard MTP:≤0.6dB(max),≤0.35(Typical)
Elite MTP:≤0.35dB(max),≤0.20dB(Typical) |
| Return loss(MPO) | ≥60dB(8degree polishing) | ≥25dB |
| Durability | <0.3dBtypical change, 200 matings | |
| Interchangeability | ≤0.2dB | |
| Tensile strength | >70N | |
| Operating Temperature | -40 to + 85°C | |
3D Interference Index
| Item (IEC-61300-3-30) | Minimum | Maximum | ||
| Radius of curvature (mm) | ROC-X(ABS) | 2000 | \ | |
| ROC-Y(ABS) | 50mm | \ | ||
| Angle | Angle-X | -0.2° | -0.2° | |
| Angle-Y | APC | 7.85° | 8.15° | |
| PC | -0.2° | -0.2° | ||
| Fiber height (nm) | 1000nm | 3500nm | ||
| Max.DH.All Fiber: | -300nm | 300nm | ||
| DH.Adj: | -300nm | 300nm | ||
| DH.Ave Fiber: | -300nm | 300nm | ||
| Core Dip: | SM | N/A | N/A | |
| MM | -200nm | 300nm | ||
MPO Connector Types
| Connector | Fiber Channel |
![]() |
![]() |
| MTP® Female Connectors | 24 Fibers |
| Note: Female connector need to connect with male connector type. | |
MTP® products’ Details& Standard:
| Connector | Reference | Housing Details |
| MTP® Singlemode | IEC 61754-7 | SM APC: Green connectors+black boot (Standard Loss MTP)
SM APC: Yellow connectors+black boot (Elite MTP) |
| MTP® Multimode | IEC 61754-7 | OM3 PC: Aqua connectors+black boot (Standard Loss&Elite MTP)
OM4 PC: Magenta connectors+black boot (Standard Loss&Elite MTP) |
- Meets IEC Standard IEC-61754-7; IEC61755, Telcordia GR-1435-CORE, JIS C5982; TIA-604-5(FOCIS5) compliant
- Structured cabling per TIA-568-C
- 10G Fiber Channel Compliant
- 40G and 100G IEEE 802.3
Cable Parameters-24F Microfiber cable


| Item | Contents | Unit | Data |
| Fiber type | / | / | SM G652D;G657A,OM1,OM2,OM3,OM4 |
| Cable diameter | ±0.3 | mm | 3.5±0.2 |
| Subunit fiber | Material | / | PVC,LSZH(CRP certification) |
| Fiber count | 24x250um | Blue,Orange,Green,Brown,Grey,White,
Red,Black,yellow,purple,pink,aqua, Blue+,Orange+,Green+,Brown+, Grey+,White+, Red+,Black+,yellow+,purple+,pink+,aqua+ |
|
| Armored unit | Material | / | SUS204 Stainless-steel Spiral Tube |
| Diameter | mm | 2.2±0.1 | |
| Strength member | Material | / | Aramid Yarn |
| Outer sheath | material | / | LSZH(CRP certification),PE,PVC,TPU,OFNP |
| Color | / | Blue,Yellow,Black, Orange,Grey,Aqua…….. | |
| Cable weight | ±5% | kg/km | 18 |
Mechanical & Environmental Performance
| Item | Contents | Value |
| Max. tensile load | Short term | 600N fiber strain≤0.6% |
| Long term | 300N | |
| Max. crush resistance | Short term | 3000N/100mm |
| Long term | 1500N/100mm | |
| Min. bending radius | Installation | 40 x cable diameter |
| Operation | 20 x cable diameter | |
| Temperature range | Operation | -20℃ ~ +70℃ |
| Installation | -20℃ ~ +60℃ | |
| Storage/transportation | -20℃ ~ +70℃ |
Flame retardant Performance
| Cable material | Standard |
| LSZH | CPR : B2ca, Cca, Dca, Eca,Fca |
| OFNP&OFNR | UL-94V0 |
Cable Jacket Material
| Item | OFNP Plenum | LSZH | OFNR Riser |
| Smoke emission | Extremely low | Very low | Heavy black smoke |
| Toxic halogen gas | None | Zero | High (chloride) |
| Fire resistance rank | Highest | Medium | Medium-low |
| Plenum air space use | Allowed | Not UL certified, restricted | Strictly prohibited |
| Vertical riser shaft | Supported | Supported | Optimized for riser shafts |
| Rigidity & hardness | Stiff, firm texture | Soft, flexible | Moderate flexibility |
| Cost | Highest | Mid-range | Lowest |
Benefits of Armored Fiber Patch Cable
Common fiber optic cable is fragile, which needs to be protected, especially when in harsh applications where cables could be compromised by rodents, constant wear and tear or weather damage. Armored fiber patch cable retains all the features of standard fiber cable but is much stronger due to its extra layers of armor. With the protection of flexible and durable steel tube, armored fiber patch cable will ensure the excellent operation of your network.

Pre-terminated MTP Technology-Polarity 24F MTP:

Length Tolerance
| Overall Length(L)(m) | length of tolerance(cm) |
| 0<L<1 | +5/-0 |
| 1<L<10 | +10/-0 |
| 10<L<40 | +15/-0 |
| 40<L | +0.5% x L/-0 |
Application:
Hyperscale DCI: Building-to-building backbones for 400G LR8, 800G DR8/FR8, and 1.6T transceivers over single-mode trunking.
5G Fronthaul/Midhaul: High-density 25G/50G/100G eCPRI links between centralized DU pools and remote radio units over distances up to 20 km.
Telecom Central Offices: High-density DWDM/OTN coherent transport, scaling wavelength multiplexing across 24 fiber lanes per trunk.
Industrial/Harsh Environments: Backbone deployment in oil/gas, mining, and manufacturing where cables face crush, vibration, and rodent threats.