1x16F MPO-2x8F MPO Conversion Cable

The 1x16F MPO to 2x8F MPO Conversion Cable (also known as a breakout / fan-out cable) is a fully passive, protocol-transparent assembly terminated with one 16-fiber MPO connector at one end and two 8-fiber MPO connectors at the other. It converts a single MPO-16 port into two MPO-8 ports (or vice versa), allowing 16-fiber parallel optics to interconnect with two 8-fiber parallel optics through one direct cable run — no splicing and no intermediate patch panel required. MTP®-compatible (MTP is a registered trademark of US Conec).

Share to:

Description

1. Design Principle

1.1 Passive Fan-out Construction

The 16 fibers of the trunk are divided into two groups of eight; each group is terminated in its own MPO-8 connector. The cable is fully passive and bidirectional — it passes light identically in either direction, with no electronics and no protocol dependency.

 

1.2 Fiber Mapping

Standard fiber mapping: trunk fibers 1–8 connect to Leg A (Pins 1–8); trunk fibers 9–16 connect to Leg B (Pins 1–8). Sequential mapping is standard; interleaved / alternate mapping is available on request.

 

1.3 Interface Compatibility

The MPO-16 ferrule holds 16 fibers in two rows of eight, matching the 16-lane parallel-optics architecture defined in IEEE 802.3df-2024 (800GBASE-SR8 / DR8), which makes MPO-16 the standard 800G interface. Factory-integrated fan-out with reinforced boots protects the fiber transition points from strain and bending.

Interface Compatibility

Fig. 1  Design principle — passive fan-out from one MPO-16 port to two MPO-8 ports (schematic, not to scale)

 

2. Polarity

Due to the complexity and variability of polarity, the fiber routing and polarity of this cable are ultimately designed according to the customer’s requirements.

Polarity Option 1

 

3. Technical Specifications

Table 1  Technical specifications

Parameter Specification
Connector — End A 1x MPO-16 / MPO-16 APC (female or male)
Connector — End B 2x MPO-8 / MPO-8 APC (female or male); 2x MPO-12 (8 fibers populated) pin-out-compatible on request
Fiber Type OM3 / OM4 / OM5 (multimode); OS2 (singlemode), bend-insensitive G.657.A2 optional
Polish MM: PC;

SM: APC (8° angled)

Insertion Loss (mated pair) SM Standard loss:≤0.75dB(max), ≤0.35dB(Typical)

SM Super Low loss:≤0.35dB(max), ≤0.20dB(Typical)

MM Standard loss:≤0.6dB(max), ≤0.35(Typical)

MM Super Low loss:≤0.35dB(max) , ≤0.20dB(Typical)

Return Loss SM ≥ 60 dB (APC);

MM ≥ 20 dB (PC)

Cable Construction Fan-out sub-units 2.0 mm; trunk 3.0–4.5 mm; jacket LSZH / OFNP / OFNR
Length Custom, 0.5–100 m
Bend Radius ≥ 10 × cable OD (dynamic)
Tensile Load (installation) ≤ 100 N
Operating Temperature −20 °C to +70 °C; storage −40 °C to +85 °C
Durability ≥ 500 mating cycles

Note: loss values are typical design targets; final values per production test report.

 

4. Material’s details

MPO Connector Types

Connector Fiber Channel
Connector11 Fiber Channel22
MPO Female Connectors 16 Fibers
Note: Female connector need to connect with male connector type.

 

Connector Fiber Channel
24f Sm Mpo Jumper Cable1227 8f Sm Mpo Mpo Jumper Cable(1)822
MPO Female Connectors 8 Fibers
Note: Female connector need to connect with male connector type.

 

5. Cable Parameters-16F Microfiber cable

16f Sm Mpo Jumper Cable272424f Om3 Mpo Jumper Cable2974

Fiber Count OD(mm) Minimum allowable

Tensile Strength (N)

minimum allowable

Crush Load(N/100mm)

Minimum Bending

Radius(MM)

16 3.0±0.15 Short-term:  150;

Long-term:  80

Short-term:  500;

Long-term:  150

Static:10D

Dynamic:20D

 

6. Standards & Compliance

Table 2  Standards and compliance

Category Standard
Connector Interface IEC 61754-7; TIA-604-5 (FOCIS-5)
Cabling & Polarity TIA-568.3-D
Performance Grades IEC 61753-021-2 (Grade B / C); Telcordia GR-326
Application (800G) IEEE 802.3df-2024
End-Face Inspection IEC 61300-3-35
Environmental / Chemical RoHS 2011/65/EU; REACH (EC) 1907/2006
Fire Safety (EU permanent installation) CPR EN 50575 / EN 13501-6
Quality System ISO 9001:2015

 

7. Length Tolerance

Length Tolerance

Overall Length(L)(m) length of tolerance(cm)
0<L<1 +5/-0
1<L<10 +10/-0
10<L<40 +15/-0
40<L +0.5% x L/-0

 

8. Quality Assurance & Testing

100% factory inspection: fiber count and continuity, insertion loss, return loss, polarity, end-face geometry and cleanliness per IEC 61300-3-35. Each cable ships with an individual test report and a polarity diagram.

Application

 

  • 800G → 2×400G breakout: 800GBASE-SR8 / DR8 to 2× 400GBASE-SR4 / DR4 optics — the standard way to fan one 800G port into two 400G ports.
  • 400G SR8 → 2× 200G SR4 fan-out.
  • AI / ML and HPC clusters: GPU-to-switch fan-out, leaf–spine high-density cabling.
  • Base-16 → base-8 conversion in structured cabling: 16-fiber trunk infrastructure connecting to devices with 8-fiber MPO interfaces.
  • Data-center moves, adds and changes (MACs) without rewiring trunk infrastructure.

Free Quote

Scroll to Top

Contact Us